- Products
- |
- Air and Water cooled Chillers
- |
- TT-14’500 H
Metric
Air-cooled chiller, water cooled version available, +10°C bis +40°CTT-14'500 H
With switchable heating - with flow control
Summary
- Temperature range +10°C up to +40°C
- Medium water
- Heating capacity 6 kW
- Cooling capacity 14 kW nominal
- Pump cpacity 75 l/min; max. 8.5 bar
- Refrigerating agent R-134a
- Ambient temperature up to +45°C
Functions
- Self-optimizing temperature controller with temperature display
1/10°C – steps - Display in °C to or °F and l/min or gal/min
- Digital flow display and monitoring
- Integrated heating
- Automatic or manual refill
Working principle
- The cooling compressor cools the content of the water tank to a required temperature
- The resultant heat leaves the unit through the rear and the side panels
Construction
- Submersible sealles pump made from bronze
- Long life expectancy due to the electronic control of the compressors operating time
- All parts in contact with water are made of stainless steel or bronze
- Unit on castors
Safety features
- Automtic level control with prewarning at low water level
- Electronic temperature limitation and monitoring in the controller
- Mechanical safety thermostats
- Visual and acoustic fault indications
- Integrated circuit breakers
- Main switch, transformer and motor protection switch
Product informationsTT-14'500 H
Product | TT-14'500 E | ||||
---|---|---|---|---|---|
Temperature range | °C | +10°C to +40°C | |||
Ambient temperatures up to | °C | +45 | |||
Refrigerating agent | R-134a | ||||
Heating capacity | kW | 6 | |||
Content water tank | l | 50 | |||
Coolin capacity nominal | kW | 14 | |||
Pump system see diagram data sheets | H | ||||
Motor | kW | 1.5 | |||
Pump pressure max. | bar | 8.5 | |||
Flow capacity max. | l/min. | 75 | |||
Flow capacity internal max. | l/min. | ||||
Compressor | hermatically sealed | ||||
Condenser air-cooled, water-cooled | |||||
Air-cooled | ⚫ | ||||
Water-cooled | ◯ | ||||
Air volume | m³/h | 2'850 | |||
Power consumption heating / cooling mode | kW | 8/5 | |||
Controller | MP-888 | ||||
Measurement sensor | Pt-100 | ||||
Connections | |||||
Flow | 3/4" BS | ||||
Return flow | 3/4" BS | ||||
Automatic water refill | 3/8" BS | ||||
Drain | 3/8" BS | ||||
Cooling water in only if water-cooled | 3/4" BS | ||||
Cooling water out only if water-cooled | 3/4" BS | ||||
Dimensions incl. castors, LxWxH | mm | 950x660x1300 | |||
Weight empty approx. | kg | 190 | |||
Colour | silvergrey RAL 7001 | ||||
Functions | ● standard/ ○ optional / - not possible | ||||
Flow control | ⚫ | ||||
Interface controller | ◯ | ||||
Version without tank | ◯ |
Imperial
Air-cooled chiller, water cooled version available, 50°F bis 104°FTT-14'500 H
With switchable heating - with flow control
Summary
- Temperature range 50°F up to 104°F
- Medium water
- Heating capacity 6 kW
- Cooling capacity 14 kW nominal
- Pump cpacity 20 gpm; max. 123 psi
- Refrigerating agent R-134a
- Ambient temperature up to 113°F
Functions
- Self-optimizing temperature controller with temperature display
1/10°F – steps - Display in °C to or °F and l/min or gal/min
- Digital flow display and monitoring
- Integrated heating
- Automatic or manual refill
Working principle
- The cooling compressor cools the content of the water tank to a required temperature
- The resultant heat leaves the unit through the rear and the side panels
Construction
- Submersible sealles pump made from bronze
- Long life expectancy due to the electronic control of the compressors operating time
- All parts in contact with water are made of stainless steel or bronze
- Unit on castors
Safety features
- Automtic level control with prewarning at low water level
- Electronic temperature limitation and monitoring in the controller
- Mechanical safety thermostats
- Visual and acoustic fault indications
- Integrated circuit breakers
- Main switch, transformer and motor protection switch
Product informationsTT-14'500 H
Product | TT-14'500 E | ||||
---|---|---|---|---|---|
Temperature range | °F | +50°F to +104°F | |||
Ambient temperatures up to | °F | +113°F | |||
Refrigerating agent | R-134a | ||||
Heating capacity | BTU/hr | 20'473 | |||
Content water tank | US gal | 13.2 | |||
Coolin capacity nominal | Rt | 4 | |||
Pump system see diagram data sheets | H | ||||
Motor | HP | 2 | |||
Pump pressure max. | psi | 123 | |||
Flow capacity max. | US gal | 20 | |||
Flow capacity internal max. | US gal | ||||
Compressor | hermatically sealed | ||||
Condenser air-cooled, water-cooled | |||||
Air-cooled | ⚫ | ||||
Water-cooled | ◯ | ||||
Air volume | cfm | 1'677 | |||
Power consumption heating / cooling mode | kW | 8/5 | |||
Controller | MP-888 | ||||
Measurement sensor | Pt-100 | ||||
Connections | |||||
Flow | 3/4" NPT | ||||
Return flow | 3/4" NPT | ||||
Automatic water refill | 3/8" NPT | ||||
Drain | 3/8" NPT | ||||
Cooling water in only if water-cooled | 3/4" NPT | ||||
Cooling water out only if water-cooled | 3/4" NPT | ||||
Dimensions incl. castors, LxWxH | inch | 37.4x26x51.2 | |||
Weight empty approx. | lbs | 419 | |||
Colour | silvergrey RAL 7001 | ||||
Functions | ● standard/ ○ optional / - not possible | ||||
Flow control | ⚫ | ||||
Interface controller | ◯ | ||||
Version without tank | ◯ |