Metric

Cooling units

Chiller +10°C bis +40°C. Available in thefollowing versions: water cooled,without tankTT-54'500

Summary

  • Temperature range +10°C up to +40°C
  • Medium water
  • Heating capacity 12 kW
  • Cooling capacity 54 kW nominal
  • Pump capacity 250 l/min; max. 6.2 bar
  • Refrigerating agent R-134a
  • Ambient temperature up to +45°C

Functions

  • Self-optimizing temperature controller with temperature display
    1/10°C – steps
  • Display in °C or °F and l/min or gal/min
  • Digital flow display and monitoring
  • Integrated heating
  • Automatic or manual refill

Working principle

  • The cooling compressor cools the content of the water tank to a required temperature
  • The resulting warm exhaust air is blown upwards by a fan

Construction

  • Proven pump with mechanical seal
  • Long life expectancy due to the electronic control of the compressors operating time
  • All parts in contact with water are made of stainless steel or bronze
  • Unit on castors

Safety features

  • Automatic level control with prewarning at low water level
  • Electronic temperature limitation and monitoring in the controller
  • Mechanical safety thermostats
  • Visual and acoustic fault indications
  • Integrated circuit breakers
  • Main switch, tansformer and motor protection switch

Cooling capacity

Pump capacity

Product informationsTT-54'500

ProductTT-54'500
Temperature range°C+10°C to +40°C
   Ambient temperatures up to°C+45
Refrigerating agentR-134a
Heating capacitykW12
Content water tankl250
Coolin capacity nominalkW54
Pump system see diagram data sheetsCR510-6
   MotorkW2.2
   Pump pressure max.bar6.2
   Flow capacity max.l/min.250
   Flow capacity internal max.l/min.
Compressorhermatically sealed
Condenser air-cooled, water-cooled
   Air-cooled
   Water-cooled
Air volumem³/h8'000
Power consumption heating / cooling modekW18/14
ControllerMP-888
   Measurement sensorPt-100
Connections
   Flow1 1/4" BS
   Return flow1 1/2" BS
   Automatic water refill3/8" BS
   Drain1" BS
   Cooling water in only if water-cooled1" BS
   Cooling water out only if water-cooled1" BS
Dimensions incl. castors, LxWxHmm1350x1050x1950
Weight empty approx.kg585
Coloursilvergrey RAL 7001
 
Functions● standard/ ○ optional / - not possible
Flow control
Interface controller
Version without tank

Imperial

Cooling units

Chiller 50°F bis 104°F  Available in thefollowing versions: water cooled,without tankTT-54'500

Summary

  • Temperature range 50°F up to 104°F
  • Medium water
  • Heating capacity 12 kW
  • Cooling capacity 54 kW nominal
  • Pump capacity 66 gpm; max. 90 psi
  • Refrigerating agent R-134a
  • Ambient temperature up to 113°F

Functions

  • Self-optimizing temperature controller with temperature display
    1/10°F – steps
  • Display in °C or °F and l/min or gal/min
  • Digital flow display and monitoring
  • Integrated heating
  • Automatic or manual refill

Working principle

  • The cooling compressor cools the content of the water tank to a required temperature
  • The resulting warm exhaust air is blown upwards by a fan

Construction

  • Proven pump with mechanical seal
  • Long life expectancy due to the electronic control of the compressors operating time
  • All parts in contact with water are made of stainless steel or bronze
  • Unit on castors

Safety features

  • Automatic level control with prewarning at low water level
  • Electronic temperature limitation and monitoring in the controller
  • Mechanical safety thermostats
  • Visual and acoustic fault indications
  • Integrated circuit breakers
  • Main switch, tansformer and motor protection switch

Cooling capacity

Pump capacity

Product informationsTT-54'500

ProductTT-54'500
Temperature range°F+50°F to +113°F
   Ambient temperatures up to°F+113°C
Refrigerating agentR-134a
Heating capacityBTU/hr40'946
Content water tankUS gal66
Coolin capacity nominalRt15.4
Pump system see diagram data sheetsCR510-6
   MotorHP3
   Pump pressure max.psi90
   Flow capacity max.gpm66
   Flow capacity internal max.gpm
Compressorhermatically sealed
Condenser air-cooled, water-cooled
   Air-cooled
   Water-cooled
Air volumecfm4'709
Power consumption heating / cooling modekW18/14
ControllerMP-888
   Measurement sensorPt-100
Connections
   Flow1 1/4" NPT
   Return flow1 1/2" NPT
   Automatic water refill3/8" NPT
   Drain1" NPT
   Cooling water in only if water-cooled1" NPT
   Cooling water out only if water-cooled1" NPT
Dimensions incl. castors, LxWxHinch53.1x41.3x76.8
Weight empty approx.lbs1290
Coloursilvergrey RAL 7001
 
Functions● standard/ ○ optional / - not possible
Flow control
Interface controller
Version without tank