1. |
  2. Products
  3. |
  4. Air and Water cooled Chillers
Cooling units

Air and Water cooled chillers with an operating range of -25°C (-13°F) to 40°C (104°F), 5 - 300 kW cooling capacity

A cooling water supply that reduces energy consumption is essential for any production facility, as the preparation of cooling water constitutes a not insignificant proportion of operation costs. Cooling water consumption represents a significant energy cost. Even more important is that the cooling system is optimally designed. The industrial water coolers from Tool-Temp guarantee an energy-saving supply of cooling water for production systems.

Temperatures

From -25°C up to 40°C
(From -13°F up to 104°F)

System

Air-cooled closed loop water chillers

Heating capacities

up to 12 kW (BTU/hr 40’946)

Cooling capacities

5 kW to 216 kW
(1.4 up to 85.3 Rt)

Refrigerating agent

R-134a

Application

Water temperatures from 10°C (50°F) to 40°C (104°F). At ambient temperatures up to 45°C (113°F)

Features

  • Flow sensor with digital indication
  • All components in contact with water are made of Corrosion resistant stainless steel or bronze
  • Long life expectancy due to the electronic control of the compressors operating time
  • Automatic or manual water refill
  • Automatic level control with prewarning at low water level

TT-5’500 E

  • Temperature range
    +10°C (50°F) up to +40°C (104°F)
  • Ambient temperature
    up to +45°C (113°F)
  • Heating capacity
    5 kW
  • Cooling capacity
    5 kW nominal
  • Pump capacity 75 l/min (20 gpm);
    max. 4.5 bar (65 psi)
  • Refrigerating agent R-134a
  • Medium water

Entry-level cooling unit

TT-14’500 H

  • Temperature range
    +10°C (50°F) up to +40°C (104°F)
  • Ambient temperature
    up to +45°C (113°F)
  • Heating capacity
    6 kW
  • Cooling capacity
    14 kW nominal
  • Pump capacity 75 l/min (20 gpm);
    max. 8.5 bar (123 psi)
  • Refrigerating agent R-134a
  • Medium water

Water cooled version available

TT-28’500

  • Temperature range
    +10°C (50°F) up to +40°C (104°F)
  • Ambient temperature
    up to +45°C (113°F)
  • Heating capacity
    9 kW
  • Cooling capacity
    28 kW nominal
  • Pump capacity 150 l/min (38 gpm);
    max. 5 bar (73 psi)
  • Refrigerating agent R-134a
  • Medium water

Following versions available: water cooled, without tank

TT-29’800 WK

  • Temperature range
    -25°C (-13°F) to +25°C (77°F)
  • Ambient temperature
    up to +45°C (113°F)
  • Cooling capacity
    54 kW nominal
  • Pump capacity 140 l/min (37 gpm);
    max. 4.8 bar (70 psi)
  • Refrigerating agent R-404a
  • Medium water

Water-cooled system for low working temperatures with water glycol

TT-54’500

  • Temperature range
    +10°C (50°F) bis +40°C (104°F)
  • Ambient temperature
    up to +45°C (113°F)
  • Heating capacity
    12 kW
  • Cooling capacity
    54 kW nominal
  • Pump capacity 250 l/min (66 gpm);
    max. 6.2 bar (90 psi)
  • Refrigerating agent R-134a
  • Medium water

Following versions available: water cooled, without tank

TT-108’000

  • Temperature range
    +10°C (50°F) bis +40°C (104°F)
  • Ambient temperature
    up to +45°C (113°F)
  • Cooling capacity
    108 kW nominal
  • Pump capacity 100 (26 gpm) / 200 (53 gpm) l/min; max. 6 (87 psi) / 4 bar (58 psi)
  • Internal circuit
    approx. 200 l/min (53 gpm)
  • Refrigerating agent R-134a
  • Medium water

Following versions available: water cooled, without tank

TT-216’000

  • Temperature range
    +10°C (50°F) to +40°C (104°F)
  • Ambient temperature
    up to +45°C (113°F)
  • Cooling capacity
    216 kW nominal
  • Pump capacity 53 / 106 gpm;
    max. 73 / 51 psi
  • Internal circuit
    approx. 500 l/min (132 gpm)
  • Refrigerating agent R-134a
  • Medium water

 

Following verisons available: water cooled, without tank

TT-300’000

  • Temperature range
    +10°C (50°F) bis +15°C (59°F)
  • Cooling capacity
    300 kW nominal
  • Internal circuit approx. 600 l/min (158.5 gpm)
  • Medium water

Extremely powerful water cooling tower